==== PAGE 1 ====
48
All Saints Church
52
Marlbrough Court
ALEXANDER
DRIVE
1
16
23
(L1, L2, L3)
(L2)
(L1)
(L2)
(L1)
Reproduced from the Isle of Man Survey map with the permission of the Department of Infrastructure, '(c) Crown Copyright'
THIS PROPOSAL PLAN MUST NOT BE USED FOR RECORD
PURPOSES OR FOR THE LOCATION OF EXISTING CABLES
PO BOX Douglas Isle of Man IM99 1PS
e: [email protected] Tel+44 (1624) 687687 www.manxutilities.im
Legend
Drawn
Checked
Approved
Date
ENE No
Rev
Wayleaves
Required
Yes/No
Scheme Instructions
DO NOT SCALE FROM THIS DRAWING
SC375762, SC374762,
SC375761, SC374761
Scale 1:250
AL240902/1
CONSERVATION AREA
A
B
C
Pavement Opening
Required
Road & Pavement
Opening Required
ROAD OPENING & TRAFFIC MANAGEMNT
REQUIRED
3 Phase Surface O/S Meter Box
Joint Location
Pot End Location
35/3/SNE lay in 125mm Rigiduct
Abandon/Remove
Additional Load to 48kVA supply capacity.
Point A to Point B lay approx. 35m of 35/3/SNE lay 125mm
Rigiduct.
At Point B terminate 35/3/SNE into 3 phase cut out and credit
meter in 3 phase surface O/S meter box. Fuse at 80A, 48kVA
ASC.
At Point A construct .15/4/PILC - 35/3/SNE service breach joint.
At Point C construct .0225/3/PILC pot end.
Point C to Point D abandon/remove existing service cable.
At Point D remove any MU equipment.
All civil works are responsibility of customer.
D
DM