# Nunnery Proposed Car Park Lighting

## PRoFESSIONAL LIGHTING DESIGN

### Nunnery Proposed Car Park Lighting

**Installation:** Road Lighting Tests **Project number:** P1658 **Customer:** McGarrigle Architects **Processed by:** J Jackson **Date:** 13.05.2016

The following values are based on exact calculations on calibrated lamps, luminaires and their arrangement. In practice, gradual divergences can occur.

Guarantee claims for luminaire data are excluded.

Relux and the luminaire manufacturers accept no liability for consequential damage and damage which is occasioned to the user or to third parties.

Relux1.rdf

Page 1/11

Object : Nunnery Proposed Car Park Lightir
Installation : Road Lighting Tests
Project number : P1658
Date : 13.05.2016

1 Exterior 1(Copy of)
PROFESSIONAL
LIGHTING
DESIGN

1.1 Description, Exterior 1(Copy of)
1.1.1 Floor plan

Relux1.rdf
Page 2/11
![A technical site plan with a 1:2500 scale showing a wooded area with blue tree symbols, a central black structure or zone, and a red winding path or road.](https://images.planningportal.im/2016/06/175877.jpg)

## 1 Exterior 1(Copy of)

[Table omitted in markdown export]

![map or plan from page 3](https://images.planningportal.im/2016/06/725889.jpg)

### 1.2 Summary, Exterior 1(Copy of)

#### 1.2.1 Result overview, Reference plane 1

Illuminance [lx]

### General

Calculation algorithm used: Average indirect fraction
Height of evaluation surface: 0.40 m
Maintenance factor: 0.80

Total luminous flux of all lamps: 200660 lm
Total power: 2044.8 W
Total power per area (9833.66 m²): 0.21 W/m² (1.78 W/m²/100lx)

### Illuminance

Average illuminance:
- Minimum illuminance: Eav 11.7 lx
- Maximum illuminance: Emin 0.1 lx
- Maximum illuminance: Emax 23.7 lx
- Uniformity g1: Emin/Em 1:89.6 (0.01)
- Uniformity g2: Emin/Emax 1:182 (0.01)

### iGuzzini

4 24
- ☐ Order No. : Composition
- ☐ Luminaire name : UFO
- ☐ Equipment : 1 x Profile 01-04 25 W / 2960 lm

6 22
- ☐ Order No. : BY83_1272_X126
- ☐ Luminaire name : Twilight
- ☐ Equipment : 1 x LED WARM 17 W / 1910 lm

## 1 Exterior 1(Copy of)

### 1.2 Summary, Exterior 1(Copy of)

#### 1.2.1 Result overview, Reference plane 1

7 10

Order No. : Composition
Luminaire name : UFO
with : 1 x subLum 1
Equipment : 1 x Profile 01-04 37 W / 4380 lm
with : 1 x subLum 2
Equipment : 1 x Profile 01-04 37 W / 4380 lm

## 1.2 Summary, Exterior 1(Copy of)

[Table omitted in markdown export]

![A technical site plan displaying topographical data, vegetation coverage in blue, and proposed access routes with coordinate axes.](https://images.planningportal.im/2016/06/725891.jpg)

### 1.2.2 Result overview, Measuring area (virtual) 1

Illuminance [lx]

#### General

Calculation algorithm used: Average indirect fraction
Height of evaluation surface: 0.12 m
Maintenance factor: 0.80

Total luminous flux of all lamps: 200660 lm
Total power: 2044.8 W
Total power per area (9833.66 m²): 0.21 W/m²

#### Illuminance

Average illuminance: Eav: 7.6 lx
Minimum illuminance: Emin: 0.7 lx
Maximum illuminance: Emax: 15.8 lx
Uniformity g1: Emin/Em: 1:11 (0.09)
Uniformity g2: Emin/Emax: 1:22.9 (0.04)

#### iGuzzini

[Table omitted in markdown export]
### 1.2 Summary, Exterior 1(Copy of)

### 1.2.2 Result overview, Measuring area (virtual) 1

7 10

Order No. : Composition
Luminaire name : UFO
with : 1 x subLum 1
Equipment : 1 x Profile 01-04 37 W / 4380 lm
with : 1 x subLum 2
Equipment : 1 x Profile 01-04 37 W / 4380 lm

## 1 Exterior 1(Copy of)

![photograph from page 7](https://images.planningportal.im/2016/06/725910.jpg)

### 1.3 Calculation results, Exterior 1(Copy of)

#### 1.3.1 3D luminance, View 1

Luminance in the scene
Minimum: $0 \mathrm{cd} / \mathrm{m}^{2}$
Maximum: $277 \mathrm{cd} / \mathrm{m}^{2}$

Object : Nunnery Proposed Car Park Lightir Installation : Road Lighting Tests Project number : P1658 Date : 13.05.2016

PROFESSIONAL LIGHTING DESIGN

## 1.3 Calculation results, Exterior 1(Copy of)

#### 1.3.2 3D luminance, View from the front

Luminance in the scene
Minimum:
Maximum:
$: 0 \mathrm{~cd} / \mathrm{m}^{2}$
$: 277 \mathrm{~cd} / \mathrm{m}^{2}$

![A dark night-time photograph showing illuminated orange ground features or temporary structures along a road, likely demonstrating lighting effects for a proposed facility.](https://images.planningportal.im/2016/06/175879.jpg)

---

*Data sourced from the Isle of Man public planning register under the [Isle of Man Open Government Licence](https://www.gov.im/about-this-site/open-government-licence/).*
*Canonical page: https://planningportal.im/a/21347-braddan-the-nunnery/documents/1320840*